Abstract:
This study aims to study the architectural elements, building status, building systems and interior space usage as well as study and recommend approaches to reduce electricity consumption and increase the electricity efficiency of the educational buildings at the faculty of Architecture, Chulalongkorn University. The survey and assess energy efficiency of the buildings have revealed that thermal transfer value of the buildings (OTTV and RTTV) are over the criteria while the efficiency of lighting system (LPD) and air-conditioning system (EER) are satisfactory. On the other hand, the infiltration rate is over the criteria. Therefore, 8 improvements are chosen and summarized into 12 possible alternatives. The alternatives are simulated with Visual DOE 4.1.0. The results show the best approach including turning off the lights and air-conditioners during lunch hours as well as closing classrooms when they are not required, installing 60 cm of horizontal and vertical shading device, changing the light bulbs to LED bulbs, replacing all glass with green glass, replacing louver window with fixed window and installing sealing rubber at the wooden door edges, installing 2 inches of fiber glass above the ceiling and installing 2 inches of fiber glass on all sides of the wall. The approach can reduce electricity consumption about 25% with the investment worth 6,302,520 baht and a payback period of 4 years and 9 months.